Skip to main content

Miniature Circuit Breakers

Miniature Circuit Breakers

Miniature circuit breakers are only used at LV, mainly in domestic or height-industrial or commercial applications. In general, they are used in the same application: as semienclosed or cartridge fuses and offer an alternative for protecting radial 01' ring circuits. They are usually only single-phase devices and have a typical rated load current range of up to 100 A with a maximum short-circuit rating of 16 kA at 240 V. Manually operated over-center spring operating mechanisms are used. Miniature circuit breakers usually employ a series overload coil for rapid short-circuit tripping and a bimetallic element for tripping on overloads. All miniature circuit breakers operate on the air-break principle where an is formed between the main contacts is forced, by means of an arc runner and the magnetic effects of the short-circuit currents, into metallic arc splitter plates. These cause a number of series arcs to be formed and at the same time extract energy from the arc and cool it to achieve arc extinction. With some designs of the Miniature circuit breaker, this is interruption process can be so rapid that the current cut-off can be achieved in much the same way as described for a current-limiting fuse. The principle of a typical miniature circuit-breaker is shown in figure 4.26.

Miniature Circuit Breakers


Miniature circuit breakers do not, however, provide rapid operation for low values of earth leakage current. Modern-day wiring regulations require that very rapid operation is achieved in the event of an earth fault to minimize the dangers from electrocution. This requires operations for earth fault currents as low as 30 mA in a time of some 2-3 ms.

A variation on the basic construction of the miniature circuit breaker is used to achieve this requirement. Such a device is commonly known as an ‘earth-leakage circuit breaker’, although the correct terminology is ‘residual-current device’. Tripping at such low values of earth leakage current is achieved by passing both the feed and return conductors through an internal current transformer. Under normal conditions, the resultant flux in the current-transformer core is zero. Under earth-fault conditions, the feeding and return currents will not be of the same value and the current difference causes the flux to be generated within the current transformer core producing an output voltage at its secondary winding terminals which are used to energize the tripping circuit of the residual current device.

The residual-current device may be permanently wired into an installation or used as plug-in devices to protect domestic electrical appliances.

One feature of the miniature circuit breaker and the residual current device is that their contacts are not maintainable and after a limited number of operations replacement of the device may be necessary. However, in practice, this is seldom a significant limitation, and eroded contacts can usually be detected by overheating causing nuisance tripping of the device.

Popular posts from this blog

Limitations of Terzaghi Theory

Limitations of Terzaghi Theory The value of the coefficient of consolidation has been assumed to be constant.  The distance d of the drainage path cannot be measured accurately in the field. The thickness of the deposit is generally variable, and an average value has to be estimated.  There is sometimes difficulty 1n locating the drainage face, sometimes thin previous seams that can act as good drainage face are missed in the boring operations. The equation is based on the assumption that the consolidation is one-dimensional. In the field, the consolidation is generally 3-dimensional. The lateral drainage may have a significant effect on the time rate of consolidation. The initial consolidation and secondary consolidation have been neglected. Sometimes these form an important part of the total consolidation. In actual practice, the pressure distribution may be far from linear or uniform. Read More Muller-Breslau principle

Price Guard Wire Method

Price Guard Wire Method Some form of  Price Guard Wire Method  is generally used to eliminate the errors caused by leakage currents over insulation. Fig. 3.14 illustrates the operation of This Method. In fig 3.14(a), a high resistance mounted on a piece of insulating material is measured by the ammeter voltmeter method. The micro-ammeter measures the sum of the current through the resistor (IR) and the current through the leakage path around the resistor. The measured value of resistance computed from the readings indicated on the voltmeter and the microammeter, will not be a true value but will be in error.   Figure 3.14 Application of  guard  circuit for measurement of high resistance In fig, 3.14 (b), the  guard  terminal has been added to the resistance terminal block. The  guard  terminal surrounds the resistance terminal entirely and is connected to the battery side of the micro-ammeter. The leakage current IL now

Negative Booster

Negative booster A negative booster is employed to conform to the regulation that the potential difference between any two points of the rail return shall not exceed 7 V. Two boosters, positive and negative, are used which are mechanically coupled together and driven by a DC motor. The positive booster is connected to the trolley wire (near the generating station) and the negative booster (separately excited) is connected to the track rail.  The 'positive booster' adds voltage to the line while the 'negative booster lowers the potential of the point it is connected to. As we go along the trolley wire away from the generating station/sub-station, the potential drop increases, and the voltage of the trolley wire falls. Since the current returns via the track rail points away from the generating station acquire high potentials. This potential is brought down by the negative boost provided by the negative booster. When the load is sufficiently far aw