Power Line Carrier System

Power Line Carrier System

A power line carrier system is used for the protection of transmission lines. The carrier currents with high-frequency range are transmitted and received with the help of transmission lines for protection. The schematic representation of the power line carrier current protection is shown in Fig. (1).

Power Line Carrier System

Equipment like transmitter, receiver, line tuning unit, master oscillator, power amplifier, etc. are provided at each end of the transmission line in this carrier's current scheme.

Various blocks in the schematic representation of power line carrier current protection are explained below:


Coupling capacitor

The various carrier equipment described 'above is connected to the transmission line with the help of the coupling capacitor. The capacitive reactance is given by l/WC. Hence for carrier frequency, it offers less reactance while high reactance for normal power frequency. It can be seen that the carrier current signals are allowed to pass through this capacitor and enter in carrier equipment while power frequency currents are blocked. The inductance connected in series with the coupling capacitor reduces the impedance to further low value. Thus a condition of resonance is achieved at the carrier frequency.


Line Trap Unit.

This unit is between the busbar and the connection of the coupling capacitor to the line. It consists of a parallel combination of inductance (L) and capacitance (C) acting as a tuned Circuit. This circuit offers low impedance to power frequency currents while offers very high impedance to carrier frequency currents which prevents the high-frequency carrier to enter the neighboring line and carrier flow only in the protected line.


Protection and Earthing of Coupling Equipment

Due to lightning, switching transients, or faults, overvoltage surges are produced on the transmission line. These overvoltages may produce stress on coupling equipment and line trap unit. For protection purposes, the nonlinear resistors are connected across the line trap unit in series with a protective gap. These resistors with protective

of the gap are connected across the inductor in the coupling unit. The length of the gap is adjusted in such a way that, spark over takes place at a set value of overvoltage. The earth rod is used is for-earthing of the coupling unit so as to get a low resistance earth path. The relay room consists of a carrier equipment panel which 1s connected to the station earthing system.


Electronic Equipment

Following electronic equipment are generally used at each end of the line,

(a) Transmitter unit

(b) Receiver unit

(c) Frequency spacing

(d) High-Frequency signal modulation


(a) Transmitter Unit:

Normally the frequencies with a range from 50 to 500 kHz are employed in various frequency bands with each has specific bandwidth. The oscillator is used for the generation of cancer frequency and it is tuned for a particular frequency which is chosen for a particular application. Sometimes a crystal oscillator may also be used which gives particular bandwidth after selecting a particular type of crystal. Voltage stabilizers are employed for maintaining the oscillator output voltage constant. The losses in the transmission path between the transmitter and receiver at the remote end of the line are overcome with the help of an amplifier which increases the level of the signal to be transmitted.

If the weather is fairly reasonable then the attenuation is of the order of 0.1 dB/kHz at 80 kHz which increases 0.2 dB/km at 380 kHz. If we‘ consider 250 km line then the output of the power amplifier is about 20 W. For a particular bandwidth, the amplifier should give maximum power. The interconnection between the oscillator and amplifier is done through the control circuit. 


(b) Receiver unit

The signal is reduced to a safe value with the help of an attenuator. The undesired signals which are signals from subsequent sections or spurious signals are prevented by using a bandpass filter. The matching element matches the impedance of the transmission line and receiving section. The undesired signals are generated either by short circuits or radio interferences. The malfunctioning of this unit is avoided due to the noise signals by using the set value above 2 milliwatts which are above the noise level. If the carrier signals have a power level of 20 W and the receiver unit is set. at a higher level of 5 milliwatts then the operation is unaffected by spurious signals. For avoiding the overloading, the signals should be attenuated before applying g it to the amplifier detector.


(c) Frequency Spacing:

The subsequent line sections use various frequencies. The carrier signals are prevented from entering into the next section by wave traps. The filters from the receiving unit filter other frequencies. The frequency, bands of various sections are properly co-ordinated.


(d) High-Frequency signal Mod:

For modulation of power frequency signals, the modulator is used. The signal after modulation is passed to the amplifier and then transmitted through the coupling unit. From the half-cycle line currents, the required blocks of carrier signals are generated with the help of an oscillator. The level of line current at which the oscillator generates these carrier blocks should be theoretically constant but practically there is a critical minimum current. The modulation of line current into high-frequency carriers is shown in the current. 

Popular posts from this blog

Limitations of Terzaghi Theory

Limitations of Terzaghi Theory The value of the coefficient of consolidation has been assumed to be constant.  The distance d of the drainage path cannot be measured accurately in the field. The thickness of the deposit is generally variable, and an average value has to be estimated.  There is sometimes difficulty 1n locating the drainage face, sometimes thin previous seams that can act as good drainage face are missed in the boring operations. The equation is based on the assumption that the consolidation is one-dimensional. In the field, the consolidation is generally 3-dimensional. The lateral drainage may have a significant effect on the time rate of consolidation. The initial consolidation and secondary consolidation have been neglected. Sometimes these form an important part of the total consolidation. In actual practice, the pressure distribution may be far from linear or uniform. Read More Muller-Breslau principle

Price Guard Wire Method

Price Guard Wire Method Some form of  Price Guard Wire Method  is generally used to eliminate the errors caused by leakage currents over insulation. Fig. 3.14 illustrates the operation of This Method. In fig 3.14(a), a high resistance mounted on a piece of insulating material is measured by the ammeter voltmeter method. The micro-ammeter measures the sum of the current through the resistor (IR) and the current through the leakage path around the resistor. The measured value of resistance computed from the readings indicated on the voltmeter and the microammeter, will not be a true value but will be in error.   Figure 3.14 Application of  guard  circuit for measurement of high resistance In fig, 3.14 (b), the  guard  terminal has been added to the resistance terminal block. The  guard  terminal surrounds the resistance terminal entirely and is connected to the battery side of the micro-ammeter. The leakage current IL now

Negative Booster

Negative booster A negative booster is employed to conform to the regulation that the potential difference between any two points of the rail return shall not exceed 7 V. Two boosters, positive and negative, are used which are mechanically coupled together and driven by a DC motor. The positive booster is connected to the trolley wire (near the generating station) and the negative booster (separately excited) is connected to the track rail.  The 'positive booster' adds voltage to the line while the 'negative booster lowers the potential of the point it is connected to. As we go along the trolley wire away from the generating station/sub-station, the potential drop increases, and the voltage of the trolley wire falls. Since the current returns via the track rail points away from the generating station acquire high potentials. This potential is brought down by the negative boost provided by the negative booster. When the load is sufficiently far aw