Skip to main content

SF6 Sulfur Hexafluoride Circuit Breaker

SF6 Sulfur Hexafluoride Circuit Breaker

SF6 Circuit Breakers Is a Circuit Breaker whose Excellent insulating, arc-extinguishing, and physical and chemical properties of SF6 gas are the greater advantages of SF6 circuit breakers. The gas is noninflammable and chemically stable.

SF6 Circuit Breaker Diagram


SF6 Sulfur Hexafluoride Circuit Breaker


What is SF6 Gas

The gas costs less if manufactured on a large scale. The gas is transported in liquid form in cylinders. Before filling the gas, the circuit breaker is evacuated  40 the pressure of about 4 mm of mercury so as to remove the moisture and air.  The gas can be reclaimed by the gas handling tank.

  • The sulfur hexafluoride possesses very good insulating properties and outstanding arc-quenching Thametcristics which make it an ideal medium for circuit inscription.

  • The physical, chemical, and dielectric properties and are-quenching characteristics of SF6 gas are given below:

  • It is colorless, odorless, non-toxic, and noninflammable gas.

  • This gas is extremely stable and inert, and its density is five times that of air.

  • It has a thermal conductivity higher (about 2-2.5 times) than that of air and assists in better cooling of current-carrying parts.

  • The gas starts liquefying at certain low temperatures. The temperature at which the SF6 gas changes to a liquid state depends on pressure. With higher pressure, this temperature increases. To avoid the liquefaction of SF6 gas the temperature of SF‘S should be maintained above a certain level. Thermostatically controlled heaters are, therefore, provided so that the gas temperature above about 16°C could be maintained in case of the high-pressure system.

  • Heat content property at a temperature below 6,000  k is much higher than that of nitrogen. The thermal time constant of SF‘S low and as a result, the pressure at which it should be stored and used is relatively smaller as compared to air.

  • Due to the electronegativity of SF6 gas, the arc ti e constant (the time between current zero and the instant the conductance of contact space reaches zero value) of SF‘S gas is very low and the rate of rising of dielectric strength is high.

  • It is chemically stable up to 500°C and does not react with structural material up to 500°C.

  • The gas is strongly electronegative, which means that free electrons are Readily removed from discharge by the formation of negative ions through processes by which a free electron is attached to a neutral gas molecule. The negative ions formed are relatively heavier and immobile as compared to free electrons and ane, therefore, ineffective as current carriers.

  • Moisture is very harmful to the properties of SF6 gas. In the presence of moisture, hydrogen Humid; is formed during arcing which can attack the metallic and insulating parts of the circuit breaker.

  • During the arc extinction process, SF6 is decomposed, into atoms, electrons, and ions. They form low molecular gaseous sulfur fluorides and compounds with the contact metals. The percentage of gaseous decomposition products have been found extremely small. These products and any other secondary gaseous reaction products are removed from the gas circuit by filters containing activated alumina (A1203) when the gas is pumped back into the high-pressure tank. The metallic fluorides are good dielectric materials and are, therefore, safe for electric equipment. However, they must be removed during periodic maintenance as they absorb moisture and lose their dielectric property. This happens if the breaker is dismantled during the rainy season.

  • The dielectric strength of SF6 gas at atmospheric pressure is 2.35 times that of air and 30% less than that of dielectric oil. At the higher pressure the dielectric strength of the gas increases. At pressure about three times the atmospheric pressure; it is more than that of oil. This property permits smaller clearances and a small size of equipment for the same voltage level.

  • They are the extinction process in SF6 circuit breakers is different from that in air blast circuit breakers. The heat is removed from the are by axial convection and radial dissipation. Turbulent flow is introduced around current zero for extinguishing the are.

  • SF6 gas, due to its electronegativity and low are time constant, regains its dielectric strength rapidly after the final current zero, the rate of rising of dielectric strength is very high and the time constant is very small SF6 is a remarkable medium for are extinction. They are extinguishing properties that are improved by moderate rates of forced gas flow through the arc space. The SFt5 gas at atmospheric pressure can interrupt currents of the order of 100 times the value of those can be interrupted in the air with a plain breaker interrupter. '

  • The basic requirement in arc extinction is not primarily the dielectric strength, but a high rate of recovery of dielectric'strength. In SF6 gas, the dielectric strength is quickly regained, as already explained. Problems connected with current chopping are, therefore minimum.

  • In the circuit. breakers, the gas is made to flow from a high-pressuredielectric strength zero to a low-pressure zone through a convergent-divergent nozzle. The nozzle is located such that the gas flows axially over the arc length. The How of gas attains almost supersonic speed in the divergent portion of the nozzle, thereby the gas takes away the heat from the arc periphery, and its diameter is reduced. The contact space is filled with fresh SF6 gas 'and its dielectric strength is rapidly regained because of the electronegativity of the gas and turbulent flow of fresh gas in the contact space.

SF6 Circuit Breaker Construction

Such a circuit breaker essentially consists of two parts, namely

(1) The interrupter unit and

(2) The gas system.


(i) The Interrupter Unit:

This unit consists of moving contact and fixed contacts comprising a set of current-carrying fingers and an arcing probe. In the 'élose position of the breaker, the fingers make contact around the circumference of the moving contact having the arcing probe enclosed within its hollow end. 

The contacts are surrounded by interrupting nozzles and blast shield to control the arc displacement and the movement of the hot gas. The moving contact is in the form of a hollow nozzle sliding in the second set of spring-loaded fingers.


(ii) The Gas System :

The closed-circuit gas system [F ig.l(b)] is employed in SF6 circuit breakers. Since the gas is costly, it is reconditioned end reclaimed after each operation of the breaker. A necessary auxiliary system is provided for such a purpose. 

The low and high-pressure systems are provided with low-pressure alarms and a set of lockout switches that give a warning the moment the gas pressure drops below a certain value,.failing which dielectric strength will be reduced and are quenching ability of the circuit breaker will be endangered. On reaching the danger limit the safety devices immobilize the breaker. 

The gas is stored in the high-pressure chamber at 16 atmospheres while the gas pressure on the low-pressure side is 3 atmospheres while the gas pressure on the low-pressure side is 3 atmospheres. A lot of care is required to prevent gas leakages at joints by providing perfect sealing. The temperature is kept at 20°C. A heater backed with a thermostat at 16°C is provided in the high-pressure chamber to prevent liquefaction of the gas in the high-pressure chamber at low temperatures.

SF6 breakers are made from 72-550 kV with rated interrupting the current of 20-63 kA and rated current of 12,000A.


SF6 Circuit Breaker Lockout 

Circuit Breaker lockout is 2 types - one that forestalls closing and therefore the other that forestalls the opening of closed CB.


I presume you're talking of the second type. It simply means it's not safe for the breaker to open under the prevailing conditions. It might be Low pressure within the case of SF6 type CBS, for instance.


In most of the cases, it's safe for the breaker to open on normal load current but not on fault, because the pressure isn't adequate for effective interruption of fault current and to stop restrike.


There is always an alarm stage before the CB goes for lockout. The alarm stage is meant to be taken seriously and schedules the isolation of the CB at the earliest, to research the explanation for low and rectify, or to exchange the CB with a spare one.


The culture of ignoring Alarms if prevalent does more harm and wishes to be addressed.


If lockout doesn't come correctly at low-pressure conditions, there could also be huge arcing within the CB contacts during operation. thanks to this, the CB may blast out with the collapse of the facility system.


So, we will understand how important is the lockout scheme of an SF6 breaker.


The lockout signal initiates from the NO (or NC as per scheme) contacts of the density monitor. Hence, we must check the lockout scheme of the CB by manually shorting the NO contact of the density monitor. We must roll in the hay once a year.



Maintenance of SF6 Circuit Breaker 

This breaker uses SF6 or sulfur hexafluoride as an arc quenching or arc extinguisher medium. Although SF6 has excellent dielectric properties. But just like the minimum oil breaker, the SF6 CB only utilizes the extinguishing property of the SF6 gas. Since this page is about the upkeep of the SF6 breaker, allow us to attend to the subject directly.


The main problem with an SF6 breaker is its leakage. An SF6 breaker may suffer from a gas leakage problem. due to that, the pressure of the gas inside the extinguisher chamber decreases.


The arc quenching capability of the breaker may deteriorate if the pressure of the gas decreases. So to avoid this, regular checking of an SF6 CB, for SF6 leakage is sort of necessary.


  • If the CB has grading capacitors, then, we'd like to see the oil leakage from grading capacitors on a monthly basis. If we found any leakage, we must immediately pile it.
  • The temperature measurement of SF6 CB could also be administered once every 3 years. Because it's good for knowing the health of the CB.
  • We also got to check the duty cycle of the CB once during a year.
  • If the pressure of the SF6 gas becomes so low, that it's going to be unable to proper arc quenching, there's a lockout within the CB. During the lockout, the CB doesn't operate.


Advantages of SF6 Circuit Breakers

  • The excellent insulating, arc-extinguishing, physical, and chemical properties of SF6 gas are the greater advantages of SF6 circuit breakers.

  • The gas is noninflammable and chemically stable.

  • Outdoor EHV SF6 circuit breaker has less number of interrupters per pole in comparison to air blast circuit breaker and minimum oil circuit breaker. An outdoor SF‘S circuit breaker is simple, comparatively cheaper in cost, maintenance-free, and compact.

  • It gives noiseless operation-it does not make 806 like air blast circuit breaker during operation.

  • No frequent contact replacement-arcing time i. small owing to outstanding arc quenching propane, of SF6 and, therefore contact erosion is less. Hence contacts do not suffer oxidation.

  • There is no reduction in the dielectric strength of SF6 since no carbon particle is formed during arcing.

  • Minimum maintenance.

  • The sealed construction avoids contamination by moisture, dust, sand, etc. No costly compressed air system is required as in the case of air blast circuit breaker.

  •  One triple pole, 145 kV SF6 circuit breaker needs only about 30 kg of SF6 gas for the first filling and no replacement is required for about 5 years.

  • No overvoltage problem. The are is extinguished at natural current zero without current chopping and associated overvoltage Originating in circuit breakers.

Oil, an obviously inflammable substance for extinguishing the hot arc, is a well-proven medium because it releases hydrogen which by virtue of its low mass and high velocity is an excellent cooling medium. But modem circuit breakers employ heavy gas SF6 as the medium for quenching the arc. SF6 gas, because of its excellent dielectric, arc quenching,  chemical, and other physical properties, has proved its superiority over another medium such as oil, or air for use in circuit breakers. Several types of SF6 circuit breakers have been developed by different Manufacturers during the last three decades for rated voltages 3.6 to769kv.


Before the 1970s in medium and high voltage range, air-break, bulk oil, minimum oil, air blast circuit breakers were in use. During the 1970’s vacuum, circuit breakers were introduced for applications up to a rated voltage of 36 kV. Single pressure puffer type SF6 breakers were introduced for rated voltages in the power system have increased.


SF6 Circuit Breaker Price

ABB Make SF6 Circuit Breaker

Rs 3.5 Lakh/Piece
Poles Number2 Pole, 3 Pole
Rated short circuit breaking capacitySF6
ClassificationType B
Power66kV to 145kV

BVM Technologies Pvt. Ltd manufactures SF6 circuit breaker switchgear

And


230 To 415 V 66 KV SF6 Circuit Breaker
Rs 8.5 Lakh/ Unit
Rated Voltage: 230 To 415 V
Frequency (Hertz): 50 Hz
Phase: Three Phase
Power Source: Electric
No Of Pole: 3 Pole

Power: 66 KV

Popular posts from this blog

RS Aggarwal Aptitude Book PDF Free Download

RS Aggarwal Aptitude Book PDF Free Download RS Agarwal Aptitude Book PDF Free Download: Quantitative Aptitude by R.S Aggarwal is a standout amongst the most inclining books among the hopefuls getting ready for Bank PO, PO, MBA, RBI, IBPS, CAT, SSC, IAS, PSC, Hotel Management, Railway Recruitment Exams, and other aggressive and placement tests. This book is suggested by different specialists in this field. This book covers relatively every theme which is being requested for the focused exams. On the off chance that you are looking to Download RS Aggarwal Quantitative Aptitude PDF's most recent version with the expectation of complimentary then you appear to be at the correct place.    Download PDF  RS Agarwal Aptitude Book PDF Free Download This book covers Problems on Surds and Indices, Simplification, Numbers and Ages, Pipes and Cisterns, Boats and Streams, Problems on Trains, Simple and Compound Interests, Time and Work, Permutations and Combination, Clocks, Odd Man Out, Heights

Limitations of Terzaghi Theory

Limitations of Terzaghi Theory The value of the coefficient of consolidation has been assumed to be constant.  The distance d of the drainage path cannot be measured accurately in the field. The thickness of the deposit is generally variable, and an average value has to be estimated.  There is sometimes difficulty 1n locating the drainage face, and sometimes thin previous seams that can act as good drainage faces are missed in the boring operations. The equation is based on the assumption that the consolidation is one-dimensional. In the field, the consolidation is generally 3-dimensional. The lateral drainage may have a significant effect on the time rate of consolidation. The initial consolidation and secondary consolidation have been neglected. Sometimes these form an important part of the total consolidation. In actual practice, the pressure distribution may be far from linear or uniform.

Comparison between VSI and CSI

Comparison between VSI and CSI In power electronic systems, inverters are an essential component that converts direct current (DC) into alternating current (AC). There are two main types of inverters used in power electronic systems: Voltage Source Inverters (VSI) and Current Source Inverters (CSI). Both have their own unique advantages and disadvantages, and the choice of which to use depends on the specific application and the desired outcome. Comparisons between voltage source inverters and current source inverters are as follows. In voltage source inverters, the input voltage is maintained constant and the amplitude of the output voltage does not depend on the load. However, the waveform of load current, as well as its magnitude, depends upon the nature of load impedance.  In current source inverters (CSI), the input current is constant but adjustable. The amplitude of output current from CSI is freelance of the load. However, the magnitude of output voltage and its undulation outp